Cable Management Systems/

Conduit System is a closed wiring system consisting of conduits and conduit fittings for the protection and management of insulated conductors, electrical cables or communication installations, allowing them to be drawn in and/or replaced, but not to be inserted laterally. Calaba provides a wide range of metallic conduit and conduit fittings for concealed, surface wiring for electrical, Tele communication appliances for all type of projects.

Material

Calaba steel Conduit pipes & fittings are manufactured with high quality grade steel, malleable cast iron and brass and protected by necessary surface coating.

Features of Calaba steel Conduit system:

• Higher mechanical properties along with good bending and
forming properties

• The threading is done accordance to British standard specification, where the conduits are supplied with socket attached on one threaded end and other threaded end with protective plastic cap.

• High quality surface protection, various coloured epoxy coatings are available based on the request.

Standard Compliance

CODES STANDARD COMPLIANCE
BS EN 61386-1 (BS EN 50086-1) Conduit systems for cable management — Part 1: General requirements.
BS EN 61386-21 (BS EN 50086-21) Conduit systems for cable management. Part 21. Particular requirements. Rigid conduit systems.
BS 4568-1 Specification for steel conduit and fittings with metric threads of ISO form for electrical installations. Steel conduit, bends and couplers.
BS 4568-2 Specification for steel conduit and fittings with metric threads of ISO form for electrical installations. Fittings and components.
BS 31 Specification. Steel conduit and fittings for electrical wiring.
BS 4662 Boxes for flush mounting of electrical accessories. Requirements, test methods and dimensions.

Calaba carries the following classes

BS 4568 -Class 3 – Medium Heavy duty Conduit

• Manufactured accordance with BS 4568 part 1 similarly known as IEC 61386-21, IEC 60614 -2-1, BS EN 61386-21, BS EN 50086-21

• Heavy protection on exterior and medium protection on interior of conduit surface

• Threaded at both ends, one end is fixed with socket and other end comes with protective plastic cap.

Nominal Size (mm) Outside Diameter (mm) Colour Wall Thickness (mm) Length of Thread Weight per Length (kg)
Min. Max. Min. Max.
16 15.7 16.0 1.4±0.10 11.5 13.5 1.2kg
20 19.7 20.0 1.6±0.15 13.0 15.0 2.7kg
25 24.6 25.0 1.6±0.15 16.0 18.0 3.4kg
32 31.6 32.0 1.6±0.15 18.0 20.0 4.5kg

Note: • Standard length 3.75 m • Customized colour finishing available based on request

BS 4568 Class 4 –Heavy duty Conduit

• Manufactured accordance with BS 4568 part 1 similarly known as IEC 61386-21, IEC 60614 -2-1, BS EN 61386-21, BS EN 50086-21

• Heavy protection on exterior on interior of conduit surface

• Threaded at both ends, one end is fixed with socket and other end comes with protective plastic cap.

Nominal Size (mm) Outside Diameter (mm) Colour Wall Thickness (mm) Length of Thread Weight per Length (kg)
Min. Max. Min. Max.
16 15.7 16.0 1.4±0.10 11.5 13.5 1.6kg
20 19.7 20.0 1.6±0.15 13.0 15.0 2.9kg
25 24.6 25.0 1.6±0.15 16.0 18.0 3.8kg
32 31.6 32.0 1.6±0.15 18.0 20.0 5.5kg

Note: • Standard length 3.75 m • Customized colour finishing available based on request